Indoor Termination Kits for 22kV Single Core Polymeric Cables

Indoor Termination Kits for 22kV Single Core Polymeric Cables

Indoor Termination Kits for 22kV Single Core Polymeric XLPE Cables

These Indoor Termination Kits for 22kV Cables are used to connect single core polymeric insulated cable to equipment.

Nexans Indoor Terminations supplied in sets of three.

Nexans Indoor Termination Kits for 22kV Cables - Specifications and Standards

Medium Voltage Terminations designed to meet the requirements of CENELEC HD 629.1

Nexans Indoor Termination Kits for 22kV Cables - Design (See Indoor Termination diagram)

22kV Indoor Termination comprising of the following components:

1. Cable lug (not included in the standard kit. price and specification available on request).
2. Water sealing mastic.
3. Silicone tube.
4. Stress control mastic.
5. Conductive EPDM ring.

Nexans Indoor Termination Kits for 22kV Cables - Selection Guide

Select the part number corresponding to both the system voltage and the cable insulation diameter in mm using the table below.

Example: The copper wire screened cable is 24 kV, 150 mm2 stranded aluminium. The diameter over core insulation is 26.2 mm. Order a 3 x ITK 224 termination kit

Indoor Termination Type Indoor Termination Reference Voltage Um (kV) Strike Distance "L" (mm) Diameter over core insulation (mm) Conductor sizes (sq.mm)
min. max. min. max.
Indoor Termination Kit - Single Core - 22kV Nexans 3 x ITK 224 24kV 260 14 33 25 240
Indoor Termination Kit - Single Core - 22kV Nexans 3 x ITK 324 24kV 300 30 50 300 800

Note: All commercialised European standard cable lugs can be used. Cable lugs must be within the dimensions specified. Please see product data sheets or contact us to ensure selection of the correct conductor connector for the appropriate dimensions

Nexans Indoor Terminations for 22kV Cables - Kit Contents

  • 3 x factory pre-assembled silicone tubes comprising stress relief and sealing mastic
  • The kit also includes water sealing mastic and installation instructions
For pricing and availability of the Nexans 22kV Indoor Termination Kits please contact us

© Bonus Power Systems 2011 All Rights Reserved | Webdesign by Vaccine Media