Outdoor Termination Kits for 11kV Single Core Polymeric Cables

Outdoor Termination Kits for 11kV Single Core Polymeric Cables

Outdoor Termination Kits for use with 11kV Single Core Polymeric XLPE Cables

Outdoor Termination Kits for 11kV Cables supplied in a set of three.

Nexans Outdoor Terminations are for Single Core Medium Voltage Cables in environments exposed to prolonged sunshine and other weather conditions.

These 11kV Outdoor Termination Kits are used to connect 11kV single core polymeric insulated cable to equipment including outdoor termination on to overhead lines or bus bars.

Nexans Outdoor Termination Kits for 11kV Cables - Design (See Outdoor Termination Drawing)

Outdoor Terminations for 11kV Single Core Cables comprise of the following components:

1. Cable lug (not included in the standard kit. price and specifications available on request).
2. Water sealing mastic.
3. Sheds which can be installed upwards or down.
4. Silicone tube with sheds.
5. Silicone tube.
6. Stress control mastic.
7. Conductive EPDM ring.

Nexans Outdoor Termination Kits for 11kV Cables - Specifications and Standards

Medium Voltage Cable Terminations designed to meet the requirements of CENELEC HD 629.1

Nexans Outdoor Termination Kits for 11kV Cables - Selection Guide (See Outdoor Termination Drawing)

Select the part number corresponding to both the system voltage and the cable insulation diameter in mm using the table below.

Example: The copper wire screened cable is 12 kV, 150 mm2 stranded aluminium with a diameter over core insulation of 26.2 mm. Order a Nexans 3 x OTK 212 outdoor termination kit.

Outdoor  Termination Type Outdoor Termination Reference Voltage Um (kV) Diameter over core insulation (mm) Conductor sizes (sq.mm)
min. max. min. max.
Outdoor Termination for 11kV Single Core Cable Nexans 3 x OTK 212 12kV 14 33 50 400
Outdoor Termination for 11kV Single Core Cable Nexans 3 x OTK 312 12kV 30 50 500

1000

 

Outdoor Termination Reference Creepage Distance "A" - "B" (mm) Strike Distance "L" (mm) Number of Sheds Fig. No.
Outdoor Termination Kit - 3 x OTK 212 420 300 3 Fig. 1
Outdoor Termination Kit - 3 x OTK 312 890 650 6 Fig. 3

Note: All commercialised European standard cable lugs can be used. Cable lugs must be within the dimensions specified. Please see product data sheets or contact us to ensure selection of the correct conductor connector for the appropriate dimensions

Nexans Outdoor Termination Kits for 11kV Cables - Contents

Nexans Outdoor Termination - OTK 212

  • 3 x factory pre-assembled silicone tubes comprising stress relief and sealing mastic
  • The kit also includes water sealing mastic and installation instructions

Nexans Outdoor Termination - OTK 312

  • 3 x factory pre-assembled silicone tubes comprising stress relief and sealing mastic
  • 3 x silicone tube with 6 sheds
  • The kit also includes water sealing mastic and installation instructions
For pricing and availability of the Nexans Outdoor Termination Kits for 11kV Cables please contact us

© Bonus Power Systems 2011 All Rights Reserved | Webdesign by Vaccine Media